Thermal Grid Sensor

POE-S2


specifications for thermal grid multi-purpose sensor

 

MULTI-SENSE SOLUTION

This is a multi-sensing solution that enables users to enact a lighting control strategy and collect valuable building operating data. Deployed either as a standalone or within a light fixture, the sensor pixelates a space and registers heat within each pixel.

REAL-TIME DATA

Real-time data collection can provide insight on room utilization and people counting when paired with an appropriate analytics engine. Thermal grid readings from the sensor are captured in one-second intervals. A restful API can send data to one of many third-party integrators for analytics and reporting.

   THERMAL GRID MOTION SENSOR
Presence sensing via thermal grid sensor.

   LIGHT LEVEL SENSOR
The light level sensor enables customers to maintain constant light levels while maximizing savings. The thermal grid sensor detects changes in sunlight to enable lights to automatically reduce power consumption.

   TEMPERATURE SENSOR
This thermal grid sensor ensures building operators and tenants are able to maintain a constant view of building operating conditions.

   HUMIDITY SENSOR
Range: 0-100% RH; typical accuracy ±2% @ 25°C (20%-80%RH); long term drift: 0.5% RH/yr).

   NODE CONNECTION
The thermal grid sensor conveniently connects to any Platformatics node. This enables users to easily add sensors anytime, anywhere.

   SENSOR AUTO DETECTION
Each thermal grid sensor is automatically detected by the node. This ensures the newly added sensors are discovered by the Area Controller. Once visible, the sensor can simply be configured to work within any zone.

 

 


   

SKU: POE-S2 Category:

Product Details

Ordering Information

PRODUCT

APPLICATION

FINISH COLOR

POE-S2-IG

PoE Thermal Grid Sensor

TR- Recessed Trim

WH White

TF- Fixture Embedded

BK  Black

TS- Surface Trim

Sample: POE-S2-IG-TR-WH

specifications

PAC Software Requirement

Minimum V2.0

Number of Pixels

64 (Vertical 8 x Horizontal 8 Matrix)

Output Temperature Range

-20°C to +80°C (-4°F to +176°F)

Temperature Accuracy

±2.5°C

Human Detection Distance

Maximum 7m (22.966ft)

Coverage

60°

Sensor Coverate

1.16 x Ceiling Height

Onboard Temperature Sensor Range

-5°C to +45°C (+23°F to +113°F)

Onboard RH Sensor Range

0-100% RH; ±2% accuracy

pixel array and viewing field

SIDE VIEW
Pixel Array (Side View)

TOP VIEW
Pixel Array (Top View)

environmental specifications

Safety Compliance

Compliant with UL 924 & UL 2108

ROHS

Compliant

DLC

DesignLights Consortium networked lighting controls systems qualified product.

Normal Operating Temperature and Altitude (Density Altitude)

-5°C to +45°C (+23°F to +113°F), up to 5000ft (1500m)

-5°C to +40°(+23°F to +104°F), up to 10,000ft (3000m)

Min ambient temperature for cold start is 0°C (+32°F)

Relative Humidity

10% to 95%, noncondensing

Storage Environment

Temperature: -20°C to +80°(-4°F to +176°F)

Location

For use in dry locations.

Mounting Options

Recessed Trim

Fixture Embedded

Surface Trim

recessed trim dimensions fixture embed dimensions surface trim dimensions

downloads

Data Sheet
Cabling and Connector Considerations