Emergency Test Button

POE-WT1


specifications for emergency test button, wall mounted with single gang

 

DEDICATED TEST BUTTON

By default, the emergency test button runs a 30-second test when pressed. Test fixtures are grouped within zones in the software.

 

 


   

SKU: POE-WS1-1 Category:

Product Details

Ordering Information

PRODUCT

CONNECTOR

POE-WT1-B-W

Emergency Test Button, Wall Mount

ST Screw Terminal

Sample: POE-WT1-B-W-ST

specifications

PAC Software Requirements

Minimum V1.1

Peripheral Communication Bus

2-twisted pairs 18-24 AWG Stranded or Solid wire 1 Pair – 1 Mbps differential data pair – CAN 2.0 (ISO 11898-2) 1 Pair – +12 VDC @ 500mAmps Maximum

Single Gang

Fits in a standard single gang mud ring or wall box.

Illumination

Programmable RGB backlight

environmental specifications

Safety Compliance

Compliant with UL 924 UL 2108

ROHS

Compliant

DLC

DesignLights Consortium networked lighting controls systems qualified product.

Normal Operating Temperature and Altitude (Density Altitude)

-5°C to +45°C (+23°F to +113°F), up to 5000ft (1500m)

-5°C to +40°(+23°F to +104°F), up to 10,000ft (3000m)

Min ambient temperature for cold start is 0°C (+32°F)

Relative Humidity

10% to 95%, noncondensing

Storage Environment

Temperature: -20°C to +80°C (-4°F to +158°F)

Altitude: 15,000ft

Location

For use in dry locations.